Planning Instruction 66571758GB0 Fire Detection 25
Sequence example 2: reset during delay
Input (e.g. MCP in alarm state)
Fire alarm device
Fire alarm device (10s delay)
Fire Output
Fire Output (10s delay)
Fire Output (12s delay)
Fire 10s 12s Re-sound
Reset
(short press)
Silence
Note!
“Silence” affects only the fire alarm device outputs.
Note!
The shortest delay is always displayed on the user interface display if more than 1 delay is activated.
6.4.3 Control group use for phased evacuation
Control groups A and B can be used to support a voice alarm fire evacuation strategy in big and/or complicated
buildings or groups of buildings.
There are numerous circumstances in which a staged fire alarm arrangement may be appropriate. One typical
application is a building with phased evacuation. In high-rise buildings, in which those closest to the fire are
evacuated in the first phase, with other areas evacuated in a series of further phases. Another application is a
progressive horizontal evacuation, e.g. in hospitals.