63230-507-201A1 Power Meter 750
03/2007 Appendix B—Register List
© 2007 Schneider Electric All Rights Reserved
47
Base + 6 Pickup Time Delay 1 Integer R/CW Y - Seconds 0 - 32767
Base + 7 Dropout Time Delay 1 Integer R/CW Y - Seconds 0 - 32767
Base + 8 Label 8 ASCII R/CW Y - -
Table B– 6: Register Listing—Alarm Setup and Status (continued)
Alarm Setup & Status
Reg Name Size Type Access NV Scale Units Range Notes
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.
Table B– 7: Register Listing—Reset Commands
Reset Commands—Write commands to Register 4126.
Command Parameters Notes
666
Restart demand metering
Does not reset Peaks
1115 Reset Meter
3211 Reset all alarms to default values
3320 De-energize digital output
3321 Energize digital output
3361 Reset digital output counter
3365 Reset digital input counters
6209
Register: Energy value to appear in register:
Preset Energy Values
7016 4000
7017 4001
7018 4002
7019 4003
7020 4004
7021 4005
10001 Clear the Usage Timers. (Set to 0)
14255 Reset all Min/Max Values. (Sets values to defaults)
21212 Reset Peak Demand values. (Set to 0)
30078 Clear all Energy Accumulators. (Set to 0)