Power Meter 750 63230-507-201
Section 5—Input/Output Capabilities 03/2007
© 2007 Schneider Electric All Rights Reserved22
Setting Up the Digital Inputs Use this procedure to set up the digital inputs.
Figure 5– 2:Demand synch pulse timing
Billing Meter
Demand Timing
Power Meter
Demand Timing
Normal Demand Mode
Billing Meter
Demand Timing
Power Meter
Demand Timing
(Slaved to Master)
External Synch Pulse Demand Timing
Utility Meter
Synch Pulse
PLSD110140
1. In SETUP mode, press ###: until D IN
(digital inputs) is visible.
2. Press D IN.
3. Select S1 or S2.
4. Select OFF or ON for NORM (normal
mode).
5. The value for SYNC (demand sync mode)
automatically changes depending on the
value selected for NORM.
6. Press OK to return to the SETUP MODE
screen.

33DSTO
 /+



$)!'
39.#
-).-8


./2-