Power Meter 750 63230-507-201A1
Appendix B—Register List 03/2007
© 2007 Schneider Electric All Rights Reserved44
Table B– 5: Register Listing—I/O Setup and Status
I/O Setup & Status
Reg Name Size Type Access NV Scale Units Range Notes
4114 Digital Output Status 1 Integer RO N - - 0 - 1
0 = Off
1 = On
4115 Digital Input S1 Status 1 Integer RO N - - 0 - 1
0 = Off
1 = On
4116 Digital Input S2 Status 1 Integer RO N - - 0 - 1
0 = Off
1 = On
4129 Digital Output Mode 1 Integer R/W Y - - 0 - 2
0 = External Control (default)
1 = Alarm Mode
2 = KWH Pulse Mode
4130 Digital Input S1 Mode 1 Integer R/W Y - - 0 - 1
0 = Normal (default)
1 = Demand Interval Synch
4131 Digital Input S2 Mode 1 Integer R/W Y - - 0 - 1
0 = Normal (default)
1 = Demand Interval Synch
4132 Digital Output Counter 2 Long RO Y - -
0 -
4,294,967,296
4134
Digital Input S1
Counter
2 Long RO Y - -
0 -
4,294,967,296
4136
Digital Input S2
Counter
2 Long RO Y - -
0 -
4,294,967,296
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.