Type Soft start units Soft start/soft stop units
Motor power 0.37 to 11 kW 0.75 to 15 kW
Degree of protection IP20
Reduction of current peaks 2 controlled phases 2 controlled phases
Adjustable starting time 1…5 s 1…10 s
Adjustable deceleration time No: freewheel stop Yes: 1... 10 s
Adjustable breakaway torque 30…80% of DOL motor starting torque
Logic inputs
–
3 logic inputs (start, stop and startup boost)
Logic outputs – 1 logic output
Relay outputs – 1 relay output
Control supply voltage
110... 220 VAC ± 10%, 24 VDC ± 10%
Built into the starter
Supply voltage
Single-phase 110…230 V
Motor power
230 V Nominal current
kW (IcL)
0.37 3 A ATS01N103FT
0.75 6 A ATS01N106FT
1.1 9 A ATS01N109FT
1.5 12 A ATS01N112FT
2.2 25 A ATS01N125FT
Supply voltage
Three-phase 110…480 V Three-phase 200…240 V Three-phase 380…415 V Three-phase 440…480 V
Motor power
210 V 230 V 400 V 460 V Nominal current
HP kW HP kW HP (IcL)
– 0.37-0.55 0.5/– 1.1 0.5-1.5 3 A ATS01N103FT – – –
0.5 0.75-1.1 1-1.5 2.2-3 2-3 6 A ATS01N106FT ATS01N206LU ATS01N206QN ATS01N206RT
11.5 2 4 5 9 A ATS01N109FT ATS01N209LU ATS01N209QN ATS01N209RT
1.5 2.2 3 5.5 7.5 12 A ATS01N112FT ATS01N212LU ATS01N212QN ATS01N212RT
– 4-5.5 5-7.5 7.5-11 10-15 22 A – ATS01N222LU ATS01N222QN ATS01N222RT
2-3 3-4-5.5 5-7.5
7
.
5-9-11
10-15 25A ATS01N125FT – – –
– 7.5 10 15 20 32 A – ATS01N232LU ATS01N232QN ATS01N232RT
Altistart 01
0.37…15 kW
Simple machines
Starters
Dimensions (in mm) width x height x depth
ATS01 N103FT/N106 FT 22.5 x 100 x 100.4
N109FT/N112 FT/N125 FT
45 x 124 x 130.7
N206pp/N209pp/N212pp
N222pp/N232pp 45 x 154 x 130.7