Section 3 — Controlling and Monitoring the ATV58 Drive Controller Bulletin No. VVDED397053US
Hand/Off/Auto (HOA) November 2000
30
© 2000 Schneider Electric All Rights Reserved
Refer to Figures 9 and 10 for assistance in designing Hand/Off/Auto
control. For the run reverse and forced local functions, select any unused
logic inputs on the main control board. Assign a logic input to the run
reverse function only if appropriate for the application.
Figure 9: Example of 2-Wire Control
NOTE: When the HOA switch is in the auto position, removing the local
run forward or run reverse commands does not stop the drive controller.
Figure 10: Example of 3-Wire Control
Local and Remote Control
The ATV58 drive controller can be commanded in local and remote
control modes.
Hand Off Auto
LI1 Run Forward
+24
LIx Run Reverse
LIy Forced Local
User
Control
Scheme
Hand Off Auto
+24
Stop
Fwd Rev
LI1 Stop
LI2 Run Forward
LIx Run Reverse
LIy Forced Local