FTB IP67 Devices
31006709 2/2009 73
Advantys FTB 1CN16CP0 Functional Description
Overview
When you open the FTB 1CN16CP0 splitter box in the Module Editor in the
Advantys configuration software, you may:
configure pin 2 on each socket to report either I/O diagnostics or the states of up
to 8 additional sensor inputs or actuator outputs (in any combination)
configure pin 4 on each socket to report the states of up to 8 additional actuator
outputs (in any combination)
set a filtering constant for each actuator output and sensor input
define the error mode and error value—i.e., the fallback mode and fallback
state—of each actuator output
Input/Diagnostic Parameter
By default, the Input/Diagnostic parameter is set to a value of 1 on each channel—
i.e., on each of the 8 M12 round sockets on the splitter box. A value of 1 indicates
that pin 2 on a socket is reporting diagnostics for the associated sensor.