Tech Data Sheet D01687GB3 Fire Detection 6
Schneider Electric Pelco Finland Oy Sokerilinnantie 11C, 02600 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103
www.pelco.com/nordic
Document Number D01687GB3 50 2012
© 2009 Schneider Electric. All rights reserved.
FXS 3NET panel external connections
Serial (RS485) communication with other FX panels (2 pcs)
Clean contact signal inputs (4 pcs), function configurable
INFO communication
REPX-OB
or
MCOX-OB
or
ZLPX-IC
Master
controller
FX-MC2
Loop controller
FX-SLC
0…1 pcs
Loop controller
FX-CLC
0…1 pcs
Output controller
FX-OCA
0…1 pcs
Input/output
controller
FX-IOC
0…1 pcs
Serial (RS232) communication with printer or maintenance tool (PC)
External communication (not in ZLPX-IC)
Fire Alarm Router Equipment (Alarm transmitter)
Fault Warning Router Equipment (Alarm transmitter)
Fire Alarm Output
Power supply outputs 24 VDC (2 pcs), short circuit protected, 500 mA each
Monitored relay outputs (4 pcs), max 500 mA each, function configurable
Power supply input 24 VDC (2 pcs) from an FX, FXL or FXM panel,
separately monitored for low voltage
Fault in Fire Alarm Router Equipment (Alarm transmitter)
Fault in Fault Warning Router Equipment (Alarm transmitter)
For each FX-SLC: Two addressable detection circuits,
each with 159 detector addresses + 159 IO-module addresses
For each FX-SLC: Power supply outputs 24 VDC (2 pcs),
short circuit protected, 500 mA each
Monitored output (Bells, sounders, beacon), 500 mA
Power supply output 24 VDC, short circuit protected, 500 mA
USB connection, maintenance tool (PC)
For each FX-CLC: 16 Conventional detection circuits, function configurable
Clean contact relay outputs (16 pcs), max 30 VDC/ 1.0 A, function configurable
Ethernet connection, INFO communication: Future option
Serial (RS485/RS232) communication with INFO/FMPX/MCOX/DAPX/REPX/ZLPX
Clean contact relay outputs (2 pcs), max 30 VDC / 1.0 A, function configurable
INFO communication
Note!
The FXS 3NET panel requires a power feed from an FX 3NET, FXL 3NET or FXM 3NET panel.
The maximum number of SLC, CLC, IOC, OCA, REPX-OB, MCOX-OB and ZLPX-IC boards is 1.