TSXCUSBMBP Settings for Concept & ProWORX32
62
35011984 02/2006
Configuring
Concept &
ProWORX32
The following steps are required to configure Concept & ProWORX32 to work the
TSXCUSBMBP:
Step Action
1 Configure the USB MBP virtual COM port, as shown in the following window:
2 Set the routing parameters if needed: (With the settings shown I can use 55, 5, or 15
to connect to the same Unity PLC.)
3 Set Concept's or ProWORX 32's Protocol to Modbus.
4 Set the Device or Port to the port USB MBP Virtual port (COM3).