Installing the Network Cable
890 USE 100 00
147
CABLE
TIE
O BLU
GND
W W
OUTER SHIELD
GROUND
WIRE
Figure 57 Drop Cable Connections
Figure 58 shows how to connect each wire. (A) Do not strip the wire.
Place the wire into the terminal slot so that the end of the wire is flush
with the inside of the terminal. (B) Using the proper insertion tool,
press the wire into the terminal. (C) Plastic caps are supplied with the
Tap. Press a plastic cap down fully into the terminal.
A B C
EMPTY
TERMINAL
TOP
VIEW
Figure 58 W ire Terminal Connection (Detail)
5.7.2 Connecting the Outer Shield W ire
Install a ground lug on the outer shield drain wire. Tightly crimp or
solder the lug to the wire. Connect the lug to the tap’s grounding screw
as shown in Figure 57.