EMC Measures for the Communications Adapter
20
32
Figure 8 Schematic of ARE lightning arrestor connection
W1 Remote Bus Line LiYCY (TP)
Z2 Grounding clamp
Outdoors
DIN-
Top hat rail
Z2
W1
Shielding
Building 1 Building 2
6 mm
2
ARE AREARE
ARE AREARE
ye
gn
br (GND)
rd
gr
br (GND)
ye
gr
rd
gn
Shielding
Protective Ground
Functional Ground
6 mm
2
Make sure to observe the following rules:
H Do not mix the wires as you run them.
H Do not mismatch the IN- and OUT ends of the ARE (IN = outdoors)
H Install a functional ground (potentialequalization rod)
H Install the lightning arrestor near the building ground so as to establish a
short discharge path for the surge current. Keep the line to the building and
functional ground (at least 6 mm2) as short as possible.
H In a remote bus line you can connect a maximum of 10 lightning arrestors in
series, with five outdoor segments which can interlink up to six buildings.